| 2013-06-06 08:51:09 | BUILDING PLAN REVIEW |
| | PERMIT: 13050164 |
| | ADD: 1801 S FLAGLER DR SUITE # PH-3 |
| | CONT: PHILLIP E JOHNSON |
| | TEL: (561)262-1795 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: JUNE 6 /2013 |
| | ACTION: DENIED |
| | CALLED CONTRACTOR 5/04/13 NO RESPONCE |
| | CALLED CONTRACTOR 5/05/13 NO RESPONCE |
| | |
| | |
| | 1) SHEET A-1 UNDER THE HEADING SITES CODE SECTION FOR |
| | BOTH FLOOR AND WALL INSULATION, RATHER THAN PROVIDING |
| | THE MANUFACTURERS SPEC ON THE MATERIAL TO BE INSTALLED |
| | ON THE FLOOR AS WELL AS WITHIN THE WALL CAVITIES FOR |
| | SOUND DEADENING. 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART... |
| | |
| | 1A) 2ND REQUEST, FLOOR INSULATION, 2010 FBC-B 1207.3 |
| | STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B)2ND REQUEST, FLOOR TILE INSULATION/ FLAME SPREAD |
| | INDEX: 2010 FBC-B 603.1(2)(1) 1. INSULATION PLACED |
| | BETWEEN TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT |
| | AN INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 100. |
| | |
| | 1C) INFORMATIONAL, COMPLIED. |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |