| 2013-05-08 17:00:26 | BUILDING PLAN REVIEW |
| | PERMIT: 13050105 |
| | ADD: 701 NORTHPOINT PKY # 400 |
| | CONT: KAST CONSTRUCTION |
| | TEL: (561)689-2910 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/08/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2 & A3 INDICATE THE USE OF SLIDING OR POCKET |
| | DOORS AS A PART OF A MEANS OF EGRESS. 2010 FBC-B 1008.1 |
| | REQUIRES PIVOT OR SIDE SWINGING DOORS, PLEASE REVIEW |
| | EXCEPTION # 1 WHICH WILL ALLOW A SLIDING DOOR WHERE THE |
| | OCCUPANT LOAD IS LESS THAN 10. |
| | |
| | 2) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS. |
| | |
| | 3) SHEET A-3 INDICATES A NEW BREAK ROOM WITH SINK, NO |
| | DETAILS WERE PROVIDED INDICATING COMPLIANCE WITH 2010 |
| | FL ACCESSIBILITY CODE |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |