2013-06-20 14:49:492010 FBC
  
 DENIED BY BUILDING
  
 1) FBC 424.1.3.1.2 REQUIRES THE POOL WET DECK TO HAVE A
 MINIMUM UNOBSTRUCTED WIDTH OF FOUR FEET. THE DECK AT
 THE NORTH END OF THE POOL IS LESS THAN 4' WIDE ON SHEET
 1 OF 5. PLEASE CORRECT. ( REPEAT COMMENT )
  
 2) THE REVISED 2010 ADA STANDARDS REQUIRE POOLS WITH
 LESS THAN 300 LINEAR FEET OF WALL TO HAVE ONE
 ACCESSIBLE MEANS OF ENTRY BY POOL LIFT OR SLOPED ENTRY.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE. FBC
 424.1.2.5.6, FBC ACCESSIBILITY 1009 ( REPEAT COMMENT )
  
 3) A MINIMUM OF TWO SETS OF PLANS ARE REQUIRED. ONLY
 ONE SHEET 3 AND ONE SHEET 5 WITH THE COLLECTOR TANK
 CHANGES WERE SUBMITTED. CITY AMENDMENTS 107.1
  