Plan Review Notes
Plan Review Notes For Permit 13050065
Permit Number 13050065
Review Stop B
Sequence Number 1
Notes
Date Text
2013-05-15 14:28:082010 FBC
  
 DENIED BY BUILDING
  
 1) FBC 424.1.3.1.2 REQUIRES THE POOL WET DECK TO HAVE A
 MINIMUM UNOBSTRUCTED WIDTH OF FOUR FEET. THE DECK AT
 THE NORTH END OF THE POOL IS LESS THAN 4' WIDE ON SHEET
 1 OF 5. PLEASE CORRECT.
  
 2) THE REVISED 2010 ADA STANDARDS REQUIRE POOLS WITH
 LESS THAN 300 LINEAR FEET OF WALL TO HAVE ONE
 ACCESSIBLE MEANS OF ENTRY BY POOL LIFT OR SLOPED ENTRY.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE. FBC
 424.1.2.5.6, FBC ACCESSIBILITY 1009
  
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 PREFABRICATED EQUIPMENT PAD SHOWING THAT IS IS CAPABLE
 OF RESISTING 170 MPH WIND SPEEDS. DCA RULE 9N-3 AND FBC
 1609.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]