| 2013-05-07 10:16:11 | FBC 2010 EXISTING BUILDING CODE |
| | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET A-8 RESTROOM DETAIL SHOWS A WIDTH OF 6' - 9". |
| | THE REQUIRED WIDTH WITH THIS CONFIGURATION WOULD BE 7' |
| | - 1" |
| | FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE |
| | AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM) |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL. |
| | FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL |
| | NOT BE PERMITTED IN THE 60" SPACE. |
| | PLEASE ALSO SEE FIGURE 604.8.1.6. |
| | |
| | 2. THE SINGLE DRINKING FOUNTAIN SHOWN ON A-8 WOULD NOT |
| | MEET THE REQUIREMENTS OF FBC ACCESSIBILITY 211.2 (HI/LO |
| | DRINKING FOUNTAINS WOULD MEET THE REQUIREMENT) |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 3. SHEET P-1 THE VENT SHOWN FOR THE SHOWER IS A |
| | HORIZONTAL DRY VENT. |
| | 905.3 VENT CONNECTION TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6 |
| | INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | ***NOTES*** |
| | 1. COUNTER TOP HEIGHT FOR THE BREAKROOM SINKS IS 34" |
| | AFF MAX. |
| | |
| | 2. THE SHOWER WILL MEET THE REQUIREMENTS OF FBC |
| | ACCESSIBILITY 608 |
| | |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |