| 2013-05-06 13:51:19 | 2744 HILLSBORO ROAD |
| | PERMIT #13050055 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 |
| | REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION |
| | WITH FLORIDA AMENDMENTS.) |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | THE PLANS INDICATE SEPARATED USE; HOWEVER, SEVERAL |
| | AREAS ARE NOT SEPARATED WITH FIRE BARRIERS. FOR |
| | EXAMPLE, THE FABRICATION AREAS (INDUSTRIAL USE) ARE NOT |
| | SEPARATED FROM THE STORAGE AREAS (STORAGE USE). ANOTHER |
| | EXAMPLE, BREAK ROOM #129 (ASSEMBLY USE) IS NOT |
| | SEPARATED FROM THE SEWING ROOM (INDUSTRIAL USE). |
| | ADEQUATE HOURLY FIRE SEPARATION SHALL BE PROVIDED IN |
| | ACCORDANCE WITH TABLE 6.1.14.4.1(A) AND (B). |
| | |
| | SEVERAL OCCUPANCIES SHOW EXIT ACCESS THROUGH AN |
| | ADJACENT OCCUPANCIES. PER SECTION 6.1.14.1.2, WHERE |
| | EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER |
| | OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| | MIXED (NON-SEPARATED) OCCUPANCY. |
| | |
| | PROVIDE AN OCCUPANT LOAD CALCULATION FOR ALL AREAS |
| | UTILIZING THE OCCUPANT LOAD FACTORS IN TABLE 7.3.1.2. |
| | |
| | THE COVER PAGE INDICATES THE BUILDING IS NOT PROTECTED |
| | BY AUTOMATIC SPRINKLERS; HOWEVER, SHEET A-5 INDICATES A |
| | TRAVEL DISTANCE OF 200 FEET FOR A BUILDING WITH |
| | SPRINKLER PROTECTION. |
| | |
| | THE PLANS SHOW LIMITED EMERGENCY LIGHTING. EMERGENCY |
| | ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1-1/2 |
| | HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. |
| | EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO |
| | PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN |
| | AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN |
| | 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT |
| | FLOOR LEVEL. |
| | |
| | PLANS SHOW RACK STORAGE. INDICATE THE STORAGE HEIGHT OF |
| | COMBUSTIBLES, THE COMMODITIES TO BE STORED, THE STORAGE |
| | ARRANGEMENT (SINGLE ROW RACK, DOUBLE ROW RACK, PALLETS, |
| | ETC.) |
| | |
| | NONE OF THE DOORS ON THE DOOR SCHEDULE ARE INDICATED AS |
| | HAVING A FIRE RESISTANCE RATING. ALSO, THE DOOR |
| | SCHEDULE INDICATES "SECURITY HARDWARE"; PLEASE INDICATE |
| | WHAT TYPE OF HARDWARE THIS IS. |
| | |
| | AT THIS TIME A COMPLETE AND THOROUGH PLAN REVIEW CANNOT |
| | BE PERFORMED DUE TO THE PLAN DESIGN COMBINING MULTIUSE |
| | (SEPARATED USE) AND MIXED USE (NON-SEPARATED USE) |
| | OCCUPANCIES. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |