Plan Review Notes
Plan Review Notes For Permit 13050041
Permit Number 13050041
Review Stop E
Sequence Number 2
Notes
Date Text
2013-05-07 08:36:155-7-13
 1. AS PREVIOUSLY REQUESTED, PLEASE PROVIDE PROPER PANEL
 SCHEDULE WITH ALL REQUIRED INFORMATION AND BREAKER
 SIZES PER NEC 408.4
 2. AFCI PROTECTION REQUIRED ON ALL NEW WORK INCLUDING
 NEW CONDUCTORS PER NEC 210.12.B
 3. AS PREVIOUSLY REQUESTED, TAMPEER RISISTANT RECPTS
 REQUIRED FOR ALL NEW AND REPLACED DEVICES PER NEC 406.4
 4. PROVIDE SMOKE ALARMS AND SHOW ON PLANS AS PER
 RESIDENTIAL CODE 314.3.1
  
 VB