| Plan Review Notes For Permit 13050041 |
| Permit Number |
13050041 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-05-07 08:36:15 | 5-7-13 | | | 1. AS PREVIOUSLY REQUESTED, PLEASE PROVIDE PROPER PANEL | | | SCHEDULE WITH ALL REQUIRED INFORMATION AND BREAKER | | | SIZES PER NEC 408.4 | | | 2. AFCI PROTECTION REQUIRED ON ALL NEW WORK INCLUDING | | | NEW CONDUCTORS PER NEC 210.12.B | | | 3. AS PREVIOUSLY REQUESTED, TAMPEER RISISTANT RECPTS | | | REQUIRED FOR ALL NEW AND REPLACED DEVICES PER NEC 406.4 | | | 4. PROVIDE SMOKE ALARMS AND SHOW ON PLANS AS PER | | | RESIDENTIAL CODE 314.3.1 | | | | | | VB |
|