2013-05-03 15:59:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC R
 301.
  
 2. EITHER PROVIDE CALCULATIONS TO SHOW THAT THE
 PROPOSED FOOTING IS ADEQUATE TO SUPPORT PROPOSED
 CONSTRUCTION OR HAVE A DESIGN PROFESSIONAL CERTIFY
 FOOTING, FBC R 301.
  
 3. FBC 107, ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4. REINFORCEMENT IS SHOWN GRAPHICALLY BUT NO
 SPECIFICATION PROVIDED; PLEASE REVISE TO INCLUDE SPEC.
  