2013-05-14 10:57:01BUILDING PROVISO:
 SHEET A2.1 ENLARGED DETAILS 3 & 4 ACCESSIBLE RESTROOMS
 FOR PRE-K CLASSROOM RESTROOMS
 THE LAVS ARE INDICATED TO BE 24" TO THE TOP OF THE
 BOWL, THE CHILDREN USING THE LAVS ARE PRE-K OR YOUNGER
 THAN 5 AND ARE TO USE A SIDE APPROACH PER 2010 FL
 ACCESSIBILITY CODE 606.2 EXCEPTION # 5. RED LINED
 DRAWINGS LAV WILL NEED TO BE CENTERED 2'-0" CENTERED
 OFF THE SIDE WALL. THE OVER ALL DIMENSION OF THE BACK
 WALL HAD TO INCREASE 2 INCHES TO ACCOMIDATE THE SIDE
 APPROACH. THE 60 INCH CLEANCE REQUIRED FOR THE WATER
 CLOSET WAS REDUCED TO 54 INCHES SINCE THIS DEMINISON IS
 TAKEN WITH THE WATER CLOSET AT 18 INCHES OFF THE WALL.
 WITH THE LOCATION OF THE WATER CLOSET AT 12 INCHES OFF
 THE WALL WE CAN USE THE 54 INCH CLEARANCE REQUIREMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676