| 2013-05-14 17:33:34 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE THE ENERGY CALCULATIONS: |
| | A) ITEM #9: ACCORDING TO PLANS THERE IS ONLY ONE 2X6 |
| | WALL WITH R19 INSULATION. OTHER WALLS ARE 2X4 WITH R11 |
| | INSULATION. REVISE TOTAL WALL AREA FOR EACH WALL TYPE |
| | TO MATCH PLANS. |
| | |
| | B) ITEM #15 IS TAKING THE "CF" AND "CV" CREDITS. |
| | PROVIDE COMPLETE SPECIFICATIONS ON PLANS SHOWING |
| | COMPLIANCE WITH THE "CV" CREDIT. SEC. 405.6.4 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C) THERE IS NOT KITCHEN ON THIS ADDITION. REVISE PAGE |
| | 2. |
| | |
| | D) REVISE ROOF TYPE AND MATERIAL ON PAGE 2 TO MATCH |
| | PLANS. |
| | |
| | E) REVISE OVERHANG DEPTH AND SEPARATION ON PAGE 3 TO |
| | MATCH PLANS. NOTE, CONSIDER THE GABLE END WALL. ALSO, |
| | THERE IS MORE THAN 6" OVERHANG SEPARATION. |
| | |
| | F) COMPLETE ALL THE INFORMATION ON TOP OF FORM. BUILDER |
| | NAME, ETC. |
| | |
| | 2- PROVIDE SITE PLAN SHOWING LOCATION AND ORIENTATION |
| | OF PROPOSED STRUCTURE. SEC. 107.3.5.3 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) STORAGE DOUBLE DOORS AS SHOWN ON FRONT ELEVATION. |
| | |
| | B) ROOF SHINGLES. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS. SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. REQUIRED |
| | BY PALM BEACH COUNTY FOR THE RECORDS RETENTION. |
| | |
| | 6- SHEET A-1: A) REVISE THE BUILDING CATEGORY AND |
| | ALTERATION LEVEL SPECIFIED ON DESIGN PARAMETERS. THIS |
| | IS TYPE "VB" NOT "II" AND IS AN ADDITION. GARAGE IS |
| | DEMOLISHED AND NEW HABITABLE BUILDING IS CONSTRUCTED. |
| | THEREFORE, SEC. 407 OF 2010-FBC-EXISTING BUILDING |
| | APPLIES. |
| | |
| | B) REVISE GENERAL NOTES AS WELL TO REFLECT ITEM #5(A) |
| | ABOVE. |
| | |
| | 7- A) REVISE ALL ROOF SHEATHING SPECIFICATIONS SHOWN ON |
| | DETAILS, WALL SECTIONS AND ROOF FRAMING NOTES. ROOF |
| | ZONE #3 NEED TO BE NAILED AT 4"O.C. AS REQUIRED BY SEC. |
| | R803.2.3.1 OF 2010-FBC-RESIDENTIAL. |
| | |
| | B) SPECIFY/IDENTIFY THE ROOF ZONE #3 FOR GABLE ENDS AS |
| | REQUIRED BY FIGURE R803.2.3.1. SPECIFY DIMENSION (5'-0" |
| | MIN.). |
| | |
| | 8- LOCATION OF ATTIC ACCESS DOESN'T PROVIDE ENOUGH |
| | HEADROOM AND IS NOT "READILY ACCESSIBLE" AS REQUIRED BY |
| | SEC. R807.1 OF 2010 FBC-RESIDENTIAL. THIS MAY BE |
| | BLOCKED BECAUSE IS LOCATED IN STORAGE ROOM AND ROOM CAN |
| | BE LOCKED. |
| | |