| Plan Review Notes For Permit 13041122 |
| Permit Number |
13041122 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-07-29 18:45:40 | RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ENGINEER SHOWN ON THE A/C PLAN TITLE BLOCK TO SIGN | | | AND DATE DRAWING AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTE. | | | | | | 2- A/C PLAN: SPECIFY THE CFM FOR EACH ROOM TO VERIFY | | | COMPLIANCE WITH THE BALANCED RETURN AREA SEC. M1602.4 | | | OF 2010 FBC-RESIDENTIAL. | | | | | | 3- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC. | | | M1602.2 OF 2010 FBC-RESIDENTIAL. CLEARLY SHOW ON A/C | | | PLAN RETURN AIR LOCATION AND SIZE. | | | | | | 4- EQUIPMENT SIZING CALCULATIONS SPECIFY UNVENTED | | | ATTIC. THIS ATTIC IS VENTED. SEE PLANS SUBMITTED. | | | REVISE AS REQUIRED. ALSO, SHOW ON A/C PLAN THE SEER | | | REQUIRED BY THE EQUIPMENT SIZING CALCULATIONS | | | SUBMITTED. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|