Plan Review Notes
Plan Review Notes For Permit 13041122
Permit Number 13041122
Review Stop M
Sequence Number 3
Notes
Date Text
2013-07-29 18:45:40RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER SHOWN ON THE A/C PLAN TITLE BLOCK TO SIGN
 AND DATE DRAWING AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 2- A/C PLAN: SPECIFY THE CFM FOR EACH ROOM TO VERIFY
 COMPLIANCE WITH THE BALANCED RETURN AREA SEC. M1602.4
 OF 2010 FBC-RESIDENTIAL.
  
 3- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC.
 M1602.2 OF 2010 FBC-RESIDENTIAL. CLEARLY SHOW ON A/C
 PLAN RETURN AIR LOCATION AND SIZE.
  
 4- EQUIPMENT SIZING CALCULATIONS SPECIFY UNVENTED
 ATTIC. THIS ATTIC IS VENTED. SEE PLANS SUBMITTED.
 REVISE AS REQUIRED. ALSO, SHOW ON A/C PLAN THE SEER
 REQUIRED BY THE EQUIPMENT SIZING CALCULATIONS
 SUBMITTED. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712