Plan Review Notes
Plan Review Notes For Permit 13041122
Permit Number 13041122
Review Stop E
Sequence Number 2
Notes
Date Text
2013-07-02 09:31:1713041122
 716 48TH ST.
 REWIRE EXISTING HOUSE
  
 PLEASE PROVIDE DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING
 SERVICE, MAIN DISCONNECT AND PANELBOARD. SHOW SERVICE
 AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING
 OUTLETS. INCLUDE A PANEL SCHEDULE. NEC 215.5
  
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE BEDROOMS
 AND HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS
 MORE THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES
 MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  
  