| 2013-07-02 09:31:17 | 13041122 |
| | 716 48TH ST. |
| | REWIRE EXISTING HOUSE |
| | |
| | PLEASE PROVIDE DETAILED ELECTRICAL PLAN FOR ALL |
| | IMPROVEMENTS. |
| | |
| | INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING |
| | SERVICE, MAIN DISCONNECT AND PANELBOARD. SHOW SERVICE |
| | AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING |
| | OUTLETS. INCLUDE A PANEL SCHEDULE. NEC 215.5 |
| | |
| | ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. |
| | NEC 210.12 |
| | |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE |
| | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A |
| | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED |
| | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC |
| | R313 |
| | |
| | ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE BEDROOMS |
| | AND HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS |
| | MORE THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES |
| | MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| | |
| | THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT |
| | AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70 |
| | |
| | A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC |
| | 250.94 |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND |
| | REAR ELEVATIONS. NEC 210.8 |
| | |
| | PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH |
| | CIRCUITS. NEC 210.52 |
| | |
| | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. |
| | NEC 210.11 (C)(3) |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | |
| | |
| | |