Plan Review Notes
Plan Review Notes For Permit 13041122
Permit Number 13041122
Review Stop B
Sequence Number 2
Notes
Date Text
2013-07-10 09:21:27RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW SECOND
 CHECKLIST.
 CODE: 2010 FBC
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3:
 A) ROOF RIDGE VENT AS SPECIFIED ON THE HCD
 "SPECIFICATIONS" BOOKLET.
  
 B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL14604-R2 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A2 SUBMITTED. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER ON PLANS AND DETAILS SUBMITTED.
  
 D) METAL SIDING AS SPECIFIED ON NOTE # 4 OF FRAMING
 LEGEND ON SHEET A2.
  
 2- ENGINEER WHO PRODUCED THE PLANS TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL THE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 3- ENGINEER TO PROVIDE SPECIFICATIONS ON PLANS FOR THE
 NEW ROOF RIDGE VENT AS SPECIFIED ON THE "HCD
 SPECIFICATIONS BOOKLET". SEE SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 4- ORIGINAL COMMENT: CITY HCD "SPECIFICATIONS" SPECIFY
 NEW PULL DOWN STAIRS FOR ATTIC ACCESS. CLARIFY IF THERE
 IS AN EXISTING PULL DOWN STAIRS. IF NOT, THEN NEED TO
 PROVIDE ENGINEERING SHOWING THAT EXISTING ATTIC IS
 ADEQUATE TO RECEIVE THE NEW STAIRS AND THAT THE ATTIC
 IS DESIGNED TO RESIST THE NEW STORAGE LOAD REQUIRED BY
 TABLE R301.5 OF 2010 FBC-RESIDENTIAL. SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
  
 RESPONSE: THERE IS NO RESPONSE TO THIS ITEM. ENGINEER'S
 PLANS SUBMITTED DIDN'T ADDRESS THIS ISSUE.
  