| 2013-07-10 09:21:27 | RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | CODE: 2010 FBC |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3: |
| | A) ROOF RIDGE VENT AS SPECIFIED ON THE HCD |
| | "SPECIFICATIONS" BOOKLET. |
| | |
| | B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL |
| | FL14604-R2 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER ON SHEET A2 SUBMITTED. SEC. |
| | R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE |
| | ENGINEER ON PLANS AND DETAILS SUBMITTED. |
| | |
| | D) METAL SIDING AS SPECIFIED ON NOTE # 4 OF FRAMING |
| | LEGEND ON SHEET A2. |
| | |
| | 2- ENGINEER WHO PRODUCED THE PLANS TO REVIEW AND |
| | APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL THE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- ENGINEER TO PROVIDE SPECIFICATIONS ON PLANS FOR THE |
| | NEW ROOF RIDGE VENT AS SPECIFIED ON THE "HCD |
| | SPECIFICATIONS BOOKLET". SEE SEC. R806 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- ORIGINAL COMMENT: CITY HCD "SPECIFICATIONS" SPECIFY |
| | NEW PULL DOWN STAIRS FOR ATTIC ACCESS. CLARIFY IF THERE |
| | IS AN EXISTING PULL DOWN STAIRS. IF NOT, THEN NEED TO |
| | PROVIDE ENGINEERING SHOWING THAT EXISTING ATTIC IS |
| | ADEQUATE TO RECEIVE THE NEW STAIRS AND THAT THE ATTIC |
| | IS DESIGNED TO RESIST THE NEW STORAGE LOAD REQUIRED BY |
| | TABLE R301.5 OF 2010 FBC-RESIDENTIAL. SEC. 107.2.1.3 OF |
| | CITY AMENDMENTS TO FBC. |
| | |
| | RESPONSE: THERE IS NO RESPONSE TO THIS ITEM. ENGINEER'S |
| | PLANS SUBMITTED DIDN'T ADDRESS THIS ISSUE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |