2013-05-16 15:23:42RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW TO DO ALL THE WORK SPECIFIED ON THE
 "SPECIFICATIONS" BOOKLET SUBMITTED. SEC. 109.3 CITY
 AMENDMENTS TO FBC.
 *** PROVIDE COPY OF SIGNED CONTRACT WITH CITY HOUSING
 AND COMMUNITY DEVELOPMENT AGENCY (HCD).
  
 2- BEDROOM WINDOWS: SPECIFY TYPE AND SIZE OF EXISTING
 WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH SEC. 601.2 AND SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3:
 A) ROOF RIDGE VENT AS SPECIFIED ON THE HCD
 "SPECIFICATIONS" BOOKLET.
  
 B) SINGLE HUNG WINDOWS. NOA 10-0428.02 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
  
 C) WINDOW MULLIONS IF THERE ARE ANY WINDOWS THAT ARE
 GOING TO BE MULLED TOGETHER.
  
 4- CITY HCD "SPECIFICATIONS" SPECIFY NEW PULL DOWN
 STAIRS FOR ATTIC ACCESS. CLARIFY IF THERE IS AN
 EXISTING PULL DOWN STAIRS. IF NOT, THEN NEED TO PROVIDE
 ENGINEERING SHOWING THAT EXISTING ATTIC IS ADEQUATE TO
 RECEIVE THE NEW STAIRS AND THAT THE ATTIC IS DESIGNED
 TO RESIST THE NEW STORAGE LOAD REQUIRED BY TABLE R301.5
 OF 2010 FBC-RESIDENTIAL. SEC. 107.2.1.3 OF CITY
 AMENDMENTS TO FBC.
  