| 2013-05-13 13:03:23 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| | ADDITIONS AS REQUIRED BY FBC ENERGY 101.4.3. |
| | |
| | 2) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION. |
| | |
| | 3) PROVIDE ADDITIONAL DETAILS OF THE FOUNDATIONS FOR |
| | THE ADDITIONS SHOWING THAT THEY COMPLY WITH FBC R403.1, |
| | R403.1.1, R403.1.2, R403.1.4, R404.1.6, R408.1 AND |
| | R408.4. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R317.1 FOR PROTECTION OF |
| | WOOD JOISTS AND WOOD STRUCTURAL FLOOR MEMBERS. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE |
| | PROTECTION. |
| | |
| | 6) SUBMIT TWO SETS OF PRODUCT APPROVALS, AS REQUIRED BY |
| | DCA RULE 9N-3, FOR THE SIMPSON CONNECTORS AND THE METAL |
| | ROOF SPECIFIED IN ITEM #2 UNDER BUILDING ENVELOPE IN |
| | THE SCOPE OF WORK ON SHEET SP-1. |
| | |
| | 7) THE WALL SECTION APPEARS TO SHOW STRUCTURAL WALL |
| | SHEATHING BEHIND THE HARDI-BOARD SIDING. PLEASE CLARIFY |
| | AND SPECIFY THE SHEATHING MATERIAL. CITY AMENDMENTS |
| | 107.2.1 |
| | |
| | 8) SHOW COMPLIANCE WITH R703.2 FOR WEATHER-RESISTANT |
| | SHEATHING PAPER ON EXTERIOR WALLS. |
| | |
| | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | MODIFIED BITUMEN ROOF SYSTEM HAS A FLORIDA COVERSHEET |
| | (FL# 5680) ATTACHED TO A MIAMI-DADE NOA. THE |
| | INSTALLATION REQUIREMENTS ARE DIFFERENT FOR EACH OF |
| | THESE. PLEASE CHOOSE THE ONE THAT YOU WANT TO USE AND |
| | SUBMIT IT. IF ENHANCED FASTENING OF THE BASE SHEET IS |
| | REQUIRED TO ACHIEVE HIGHER UPLIFT FOR THE CORNER AND |
| | PERIMETER ROOF AREAS, THEN SUBMIT TWO SETS OF SIGNED |
| | AND SEALED RAS 117 CALCULATIONS. DCA RULE 9N-3. |
| | |
| | 10) SUBMIT TWO SETS OF A KEY PLAN AND AN INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS (FL# 10905-R1) THAT WERE |
| | SUBMITTED. |
| | |
| | 11) SHOW COMPLIANCE WITH FBC R314.3.1 FOR INSTALLATION |
| | OF SMOKE ALARMS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |