| Plan Review Notes For Permit 13041056 |
| Permit Number |
13041056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-06 10:53:36 | 5-6-13 | | | 1. PROVIDE ENGINEERED MOUNTING DETAILS FOR 75 KVA | | | CEILING HUNG TRANSFORMER | | | 2. PROVIDE ELECTRICAL RISER DIAGRAM AND FAULT CURRENTS | | | - NEC 110.9, 110.10, 215.5 | | | 3. PROVIDE PANEL SCHEDULES PER NEC 408.4 FOR | | | CLARIFICATION PURPOSES | | | | | | VB |
|