Plan Review Notes
Plan Review Notes For Permit 13041056
Permit Number 13041056
Review Stop E
Sequence Number 1
Notes
Date Text
2013-05-06 10:53:365-6-13
 1. PROVIDE ENGINEERED MOUNTING DETAILS FOR 75 KVA
 CEILING HUNG TRANSFORMER
 2. PROVIDE ELECTRICAL RISER DIAGRAM AND FAULT CURRENTS
 - NEC 110.9, 110.10, 215.5
 3. PROVIDE PANEL SCHEDULES PER NEC 408.4 FOR
 CLARIFICATION PURPOSES
  
 VB