| 2013-04-26 17:20:52 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE CURRENT PRODUCT APPROVAL (2 COPIES) AS | | | REQUIRED BY DCA RULE 9N-3 FOR THE ROOF SHINGLES. NOA | | | 12-0227.18 SUBMITTED EXPIRED ON 04/22/13. NEED CURRENT | | | ONE. | | | | | | 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED: PROVIDE THE | | | RAS 117 CALCULATIONS FOR THE NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. NEED THE | | | NAIL ENHANCING TO MEET THE DESIGN PRESSURES REQUIRED BY | | | SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|