| 2013-04-30 13:43:29 | AHU 1 - MAX BREAKER SHOULD BE 50 AMP, DRAWINGS SHOW 60 | | | AMP | | | AHU2 - MAX BREAKER SHOULD BE 30 AMO, DRAWINGS SHOW 60 | | | AMP | | | | | | BOTH AHU'S LABELED #1 | | | | | | CU1 - MAX BREAKER SHOULD BE 25 AMP, DRAWINGS SHOW 40 | | | AMP | | | CU2 - MAX BREAKER SHOULD BE 30 AMP, DRAINGS SHOW 30 AMP |
|