Plan Review Notes
Plan Review Notes For Permit 13040963
Permit Number 13040963
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-30 13:43:29AHU 1 - MAX BREAKER SHOULD BE 50 AMP, DRAWINGS SHOW 60
 AMP
 AHU2 - MAX BREAKER SHOULD BE 30 AMO, DRAWINGS SHOW 60
 AMP
  
 BOTH AHU'S LABELED #1
  
 CU1 - MAX BREAKER SHOULD BE 25 AMP, DRAWINGS SHOW 40
 AMP
 CU2 - MAX BREAKER SHOULD BE 30 AMP, DRAINGS SHOW 30 AMP