2013-04-24 15:06:12****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. APPLICATION STATES THAT 21 WINDOWS ARE TO BE
 INSTALLED, FLOOR PLAN SHOWS FEWER. IF SOME WINDOWS ARE
 DOUBLE WINDOWS, PROVIDE THE MULLION PRODUCT APPROVAL
 FAC9N-3 AND REVISE PLAN TO INDICATE DOUBLE WINDOWS.
  
 2. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 3. PROVIDE A COPY OF THE RECEIPT FOR THE WINDOWS FBC
 107. VALUE IS TOO LOW. VALUE TO INCLUDE LABOR,
 MATERIALS, MARKUP, OVERHEAD, ETC.
  