2013-06-12 09:05:382010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE A SITE PLAN OR SURVEY THAT SPECIFIES THE
 DISTANCE TO THE PROPERTY LINE ON THE SIDE OF THE GARAGE
 WHERE THE PROPOSED WINDOW IS LOCATED. SEE FBCR302.1 AND
 TABLE R302.1 FOR REQUIRED FIRE SEPARATION DISTANCE FOR
 OPENINGS.
  
 2) THE OCCUPANCY, TYPE OF CONSTRUCTION AND LEVEL OF
 ALTERATION ON SHEET A-1 ARE INCORRECT. THIS IS A SINGLE
 FAMILY RESIDENCE WHICH IS AN R-3 OCCUPANCY (FBC SECTION
 310.1), THE TYPE OF CONSTRUCTION IS VB (FBC SECTION
 602) AND IT IS A LEVEL 2 ALTERATION PER FBC EXISTING
 BUILDING SECTION 404. PLEASE CORRECT.
  
 3) SPECIFY THE WINDSPEED AND EXPOSURE CATEGORY FOR THIS
 PROJECT ON THE PLANS. THE WINDSPEED IS 170 MPH VULT /
 132 VASD AND THE EXPOSURE CATEGORY IS C. FBC R301.2.1.1
 AND R301.2.1.4.3
  
 4) SHOW COMPLIANCE WITH FBC ENERGY SECTION 402 BY
 SUBMITTING THE REQUIRED ENERGY COMPLIANCE FORMS FOR THE
 PROPOSED HABITABLE SPACE.
  
 5) SHOW COMPLIANCE WITH FBC R314 .3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 6) THE TITLE BLOCK ON THE PLAN SHEETS ARE MISSING SOME
 OF THE MINIMUM INFORMATION REQUIRED BY FAC 61G1-16.004.
 PLEASE INCLUDE THE LICENSE NUMBER OF THE ARCHITECTURAL
 FIRM AND THE PRINTED NAME OF THE PERSON SEALING THE
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]