| 2013-04-30 12:06:31 | 1608 SOUTH DIXIE HIGHWAY |
| | PERMIT #13040934 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | RESPONSE COMMENT: "GENERAL COMMERCIAL" IS NOT AN |
| | OCCUPANCY TYPE. IF THIS PERMIT IS FOR A SHELL PERMIT |
| | ONLY WITH NO TENANT PLEASE INDICATE. |
| | ORIGINAL COMMENT: PLANS DO NOT INDICATE THE OCCUPANCY |
| | TYPE THAT WILL BE OCCUPYING SPACE 3 & 4. |
| | |
| | RESPONSE COMMENT: PROVIDE DRAWING NOTE INDICATING WALL |
| | TO BE PERMANENTLY IDENTIFIED WITH THE NOTE BELOW. |
| | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. REFERENCE |
| | SECTION 8.3.2.4 OF FLORIDA FIRE PREVENTION CODE - NFPA |
| | 101 |
| | |
| | RESPONSE COMMENT: NO EGRESS INFORMATION PROVIDED FOR |
| | SPACE #6. |
| | ORIGINAL COMMENT: THE NEW FIRE BARRIER APPEARS TO |
| | ELIMINATE AN EXIT FROM SPACE #6. SHOW THE EXIT DOORS |
| | AND TRAVEL DISTANCES FOR SPACE #6. |
| | |
| | RESONSE COMMENT: INDICATE THE EXISTING LOCATIONS AND |
| | DIMENSION THE EXISTING SPRINKLER LOCATIONS WITH |
| | REFERENCE TO THE NEW PROPOSED WALL TO CONFIRM TO NO |
| | SPRINKLER ADDITIONS OR RELOCATIONS ARE REQUIRED. |
| | SEPARATE PLANS AND PERMITS ARE NEEDED TO RELOCATE THE |
| | EXISTING SPRINKLERS AROUND THE NEW FIRE BARRIER. |
| | |