| Plan Review Notes For Permit 13040905 |
| Permit Number |
13040905 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-15 18:27:29 | HEIGHT OF ELECTRICAL RECEPTACLES IS AT THE LIMIT OF A | | | CLASSIFIED AREA (ZONE). | | | LOCATION MAY BE A CLASSIFIED AREA AS CLASS 1 DIVISION | | | 2, AND ALSO MAY FALL UNDER NEC ARTICLE 511. | | | PROVIDE INFORMATION AND LOCATION OF EXISTING AND | | | PROPOSED CONDUITS, SEALOFFS AND OTHER ITEMS RELATED THE | | | CLASSIFIED LOCATION. | | | PROVIDE DETAILS OF MATERIALS AND WIRING METHODS | | | SPECIFIED AND REQUIRED. | | | IF AREA IS TO BE UNCLASSIFIED, PLEASE PROVIDE | | | DOCUMENTATION MEETING THE REQUIREMENTS OF THE NEC TO | | | SHOW COMPLIANCE. | | | IF AREA IS USED FOR NON-TRADITIONAL FUELS, SUCH AS | | | HYDROGEN, ADDRESS AREA WITHIN 18" OF THE CEILING. |
|