2013-08-15 18:27:29HEIGHT OF ELECTRICAL RECEPTACLES IS AT THE LIMIT OF A
 CLASSIFIED AREA (ZONE).
 LOCATION MAY BE A CLASSIFIED AREA AS CLASS 1 DIVISION
 2, AND ALSO MAY FALL UNDER NEC ARTICLE 511.
 PROVIDE INFORMATION AND LOCATION OF EXISTING AND
 PROPOSED CONDUITS, SEALOFFS AND OTHER ITEMS RELATED THE
 CLASSIFIED LOCATION.
 PROVIDE DETAILS OF MATERIALS AND WIRING METHODS
 SPECIFIED AND REQUIRED.
 IF AREA IS TO BE UNCLASSIFIED, PLEASE PROVIDE
 DOCUMENTATION MEETING THE REQUIREMENTS OF THE NEC TO
 SHOW COMPLIANCE.
 IF AREA IS USED FOR NON-TRADITIONAL FUELS, SUCH AS
 HYDROGEN, ADDRESS AREA WITHIN 18" OF THE CEILING.