Plan Review Notes
Plan Review Notes For Permit 13040905
Permit Number 13040905
Review Stop P
Sequence Number 1
Notes
Date Text
2013-07-15 09:19:40FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVISION #1
 DENIED:
  
 SHEET A-1: THE DETAIL FOR ACCESSIBILITY HAS BEEN
 REMOVED. THE RESTROOM APPEARS TO HAVE NO GRAB BARS AND
 THE LAVITORY IS SHOWN IN THE 60" CLEAR SPACE FOR THE
 WATER CLOSET.
 604.8.1.5 GRAB BARS.
 GRAB BARS SHALL COMPLY WITH 609. A SIDE-WALL GRAB BAR
 COMPLYING WITH 604.5.1 SHALL BE PROVIDED AND SHALL BE
 LOCATED ON THE WALL CLOSEST TO THE WATER CLOSET. IN
 ADDITION, A REAR-WALL GRAB BAR COMPLYING WITH 604.5.2
 SHALL BE PROVIDED.
 604.8.1.6 LAVATORY.
 IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN
 IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES
 DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR
 ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH
 SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART
 OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE
 ALSO SECTION 213.3.4.
  
  