| Notes |
| Date |
Text |
| 2013-08-09 15:20:51 | PLAN DENIED | | | 1) PROVIDE NOA ON CONDENSER STAND . | | | PER SECTION 107 FBC 2010 | | | 2) PROVIDE A DETAIL FROM THE ENGINEER | | | ON THE CONDENSER STAND TO ROOF TIEDOWN | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|