Plan Review Notes
Plan Review Notes For Permit 13040905
Permit Number 13040905
Review Stop M
Sequence Number 1
Notes
Date Text
2013-08-09 15:20:51PLAN DENIED
 1) PROVIDE NOA ON CONDENSER STAND .
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CONDENSER STAND TO ROOF TIEDOWN
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER