| Plan Review Notes For Permit 13040902 |
| Permit Number |
13040902 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-27 18:48:55 | 411 CLEMATIS STREET | | | PERMIT #13040902 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO SUITE NUMBER PROVIDED ON PERMIT APPLICATION OR | | | DRAWINGS. | | | | | | A NEW FIRE-RATED WALL APPEARS TO BE NEEDED BETWEEN | | | TENANT SPACE #D2.107 AND SPACE #D2.202. PROVIDE A WALL | | | DETAIL. | | | | | | PLANS DO NOT INDICATE IF ANY DUCTWORK WILL BE PASSING | | | THROUGH THE NEW TENANT SEPARATION WALL. | | | | | | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE | | | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED | | | WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM | | | OR DEVICE. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|