| 2013-04-29 14:52:45 | 4200 NORTH FLAGLER DRIVE | | | PERMIT #13040851 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101 | | | REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION | | | WITH FLORIDA AMENDMENTS.) | | | | | | WITH THE CONVERSION OF THE MEZZANINE AREA INTO A TRUE | | | SECOND STORY, TWO EXITS ARE REQUIRED FROM THE SECOND | | | FLOOR. PER SECTION 38.2.4.1, NOT LESS THAN TWO SEPARATE | | | EXITS SHALL BE PROVIDED ON EVERY STORY; THEREFORE, THE | | | EXISTING UNPROTECTED INTERIOR STAIR SHALL BE ENCLOSED | | | AND HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING WHERE | | | THE EXIT CONNECTS THREE OR FEWER STORIES PER SECTION | | | 7.1.3.2.1. | | | | | | PER SECTION 7.1.3.2.1(9), PENETRATIONS INTO, AND | | | OPENINGS THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE | | | LIMITED TO SERVICES ESSENTIAL TO THE FUNCTION OF THE | | | STAIR. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|