Plan Review Notes
Plan Review Notes For Permit 13040851
Permit Number 13040851
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-04-29 14:52:454200 NORTH FLAGLER DRIVE
 PERMIT #13040851
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
 WITH THE CONVERSION OF THE MEZZANINE AREA INTO A TRUE
 SECOND STORY, TWO EXITS ARE REQUIRED FROM THE SECOND
 FLOOR. PER SECTION 38.2.4.1, NOT LESS THAN TWO SEPARATE
 EXITS SHALL BE PROVIDED ON EVERY STORY; THEREFORE, THE
 EXISTING UNPROTECTED INTERIOR STAIR SHALL BE ENCLOSED
 AND HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING WHERE
 THE EXIT CONNECTS THREE OR FEWER STORIES PER SECTION
 7.1.3.2.1.
  
 PER SECTION 7.1.3.2.1(9), PENETRATIONS INTO, AND
 OPENINGS THROUGH, AN EXIT ENCLOSURE ASSEMBLY SHALL BE
 LIMITED TO SERVICES ESSENTIAL TO THE FUNCTION OF THE
 STAIR.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730