| 2013-05-31 11:24:19 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO COPIES OF A SOIL INVESTIGATION REPORT |
| | FROM A FLORIDA LICENSED GEOTECHNICAL ENGINEER. FBC |
| | R401.4 |
| | |
| | 2) THE PLANS INDICATE ASPHALT SHINGLES ON THE 1-3/4" / |
| | 12" SLOPE AT THE COVERED PORCH AND DEN SECTIONS. FBC |
| | R905.2.2 STATES THAT ASPHALT SHINGLES SHALL ONLY BE |
| | USED ON ROOF SLOPES OF 2" / 12" OR GREATER. PLEASE |
| | CORRECT. |
| | |
| | 3) THE EXISTING CONCRETE SLAB AT THE COVERED PORCH |
| | SHOULD BE REMOVED OR PROPERLY TIED TO THE NEW SLAB TO |
| | PREVENT UNEVEN SETTLEMENT. ACI 318 AND ACI 302.1 |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES |
| | CONCRETE FOUNDATION WALLS TO EXTEND A MINIMUM OF 4 |
| | INCHES ABOVE THE FINISHED ADJACENT GRADE WHERE MASONRY |
| | IS USED. |
| | |
| | 6) THE ENERGY FORM 402 - 2010 CONTAINS SOME INCORRECT |
| | INFORMATION. THE WINDOWS ARE REQUIRED TO HAVE A SOLAR |
| | HEAT GAIN COEFFICIENT OF 0.30 OR LESS AND THE MASS WALL |
| | INSULATION IS REQUIRED TO BE A MINIMUM OF R-7.8 IF MORE |
| | THAN HALF OF THE INSULATION IS ON THE INTERIOR OF THE |
| | MASS WALL. FBC ENERGY TABLE 402.1.1 |
| | |
| | 7) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. CITY AMENDMENTS 107.3.4.1 |
| | |
| | 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | SIMPSON FSA, MSTAM24, AND H2.5 ANCHORS SPECIFIED ON THE |
| | PLANS. DCA RULE 9N-3 |
| | |
| | 9) THE PRODUCT APPROVAL FOR THE STORM PANELS (NOA NO. |
| | 09-0330.04) HAS BEEN SUPERSEDED. PLEASE SUBMIT THE |
| | CURRENT PRODUCT APPROVAL. |
| | |
| | 10) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | OPENINGS THAT THE STORM PANELS WILL BE INSTALLED ON. |
| | CITY AMENDMENTS 107.2.1 |
| | |
| | 11) THE PRODUCT APPROVALS FOR THE STEEL DOOR NOA NO. |
| | 08-0208.07 AND SINGLE HUNG WINDOWS FL 239-R1 ARE |
| | EXPIRED. PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL. |
| | |