Plan Review Notes
Plan Review Notes For Permit 13040804
Permit Number 13040804
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-22 12:56:31WIRE SIZE NOT PER NEC 310-15
 SHOW DETAILS OF INSTALLATION INCLUDING SIDE VIEW WITH
 CLEARANCES 230.9, 230.24
 WHAT IS THE PURPOSE OF THE RELOCATION?
 WHERE WILL FEEDER CONDUIT BE LOCATED? ABOVE GROUND,
 UNDERGROUND, ATTIC, ETC. MUST MEET NEC REQUIREMENTS FOR
 INSTALLATION
 WHERE IS THE MAIN DISCONNECT? ARTICLE 230
 IS METER TO BE RELOCATED OR NEW? DRAWING SHOWS BOTH
 PROVIDE WIRE SIZE FOR GES 250 PART III
 PROVIDE INTERSYSTEM BONDING POINT 250.94
 CHANGES TO PLANS MAY REQUIRE ADDITIONAL INFORMATION