| Plan Review Notes For Permit 13040804 |
| Permit Number |
13040804 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-22 12:56:31 | WIRE SIZE NOT PER NEC 310-15 | | | SHOW DETAILS OF INSTALLATION INCLUDING SIDE VIEW WITH | | | CLEARANCES 230.9, 230.24 | | | WHAT IS THE PURPOSE OF THE RELOCATION? | | | WHERE WILL FEEDER CONDUIT BE LOCATED? ABOVE GROUND, | | | UNDERGROUND, ATTIC, ETC. MUST MEET NEC REQUIREMENTS FOR | | | INSTALLATION | | | WHERE IS THE MAIN DISCONNECT? ARTICLE 230 | | | IS METER TO BE RELOCATED OR NEW? DRAWING SHOWS BOTH | | | PROVIDE WIRE SIZE FOR GES 250 PART III | | | PROVIDE INTERSYSTEM BONDING POINT 250.94 | | | CHANGES TO PLANS MAY REQUIRE ADDITIONAL INFORMATION |
|