2013-05-09 12:48:39OK FOR FOUNDATION ONLY. ALL ITEMS TO BE ADDRESSED PRIOR
 TO ADDITIONAL PERMITTING.
  
  
 PLAN STATES THE BUILDING IS A CORROSIVE LOCATION.
 PLEASE DEFINE THE LEVEL OF HAZARD AND IF ANY GASSES OR
 DUST WILL BE PRESENT TO REQUIRE A CLASSIFICATION AS A
 HAZARDOUS LOCATION AND TO WHAT LEVEL THE HAZARD WILL
 EXIST.
 ALL CONDUIT IS BEING REQUIRED TO BE PVC COATED AND ALL
 PULL BOXES ARE BEING REQUIRED TO BE 316 STAINLESS. DOES
 THIS REQUIREMENT GO TO FIXTURES, DEVICES AND OTHER
 EQUIPMENT OR MATERIALS IN THE STRUCTURE?
 WILL SPLICES NEED TO BE ENCAPSULATED OR PROTECTED DUE
 TO HAZARDOUS ENVIRONMENT?
 REVIEW CANNOT BE COMPLETED UNTIL QUESTIONS ARE ANSWERED
  