| Plan Review Notes For Permit 13040783 |
| Permit Number |
13040783 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-09 12:48:39 | OK FOR FOUNDATION ONLY. ALL ITEMS TO BE ADDRESSED PRIOR | | | TO ADDITIONAL PERMITTING. | | | | | | | | | PLAN STATES THE BUILDING IS A CORROSIVE LOCATION. | | | PLEASE DEFINE THE LEVEL OF HAZARD AND IF ANY GASSES OR | | | DUST WILL BE PRESENT TO REQUIRE A CLASSIFICATION AS A | | | HAZARDOUS LOCATION AND TO WHAT LEVEL THE HAZARD WILL | | | EXIST. | | | ALL CONDUIT IS BEING REQUIRED TO BE PVC COATED AND ALL | | | PULL BOXES ARE BEING REQUIRED TO BE 316 STAINLESS. DOES | | | THIS REQUIREMENT GO TO FIXTURES, DEVICES AND OTHER | | | EQUIPMENT OR MATERIALS IN THE STRUCTURE? | | | WILL SPLICES NEED TO BE ENCAPSULATED OR PROTECTED DUE | | | TO HAZARDOUS ENVIRONMENT? | | | REVIEW CANNOT BE COMPLETED UNTIL QUESTIONS ARE ANSWERED | | | |
|