| Plan Review Notes For Permit 13040744 |
| Permit Number |
13040744 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-23 07:01:05 | NO MECHANICAL SHOWN TO INDICATE EXISTING OR NEW. | | | PLUMBING NOT SHOWN, GAS WATER HEATER SHOWN WITHOUT | | | INDICATION AS TO EXISTING OR NEW | | | PROVIDE ENERGY CODE CALCS | | | SMOKE DETECTOR NOT PERMITTED ON BATH CICUIT AS CALLED | | | FOR - 210.11C | | | LOAD CALC DOES NOT MATCH PANEL SCHEDULE | | | WIRE SIZING TO BE PER TABLE 310-16, UNLESS EXCEPTIONS | | | APPLY | | | REVIEW STOPPED |
|