| Notes |
| Date |
Text |
| 2013-05-06 10:05:23 | PLANS DENIED | | | 1) PROVIDE DUCT SIZE IN CLASS ROOM # 4. PER | | | SECTION 107 FBC 2010 | | | 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S. | | | 2010 FBC (M) | | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS | | | 606.3 INSTALLATION AND 606.4.1 SUPERVISION 2010 FBC (M) | | | 4) PROJECT SUMMARY MUST BE SIGNED AND SEALED BY AN | | | ENGINEER | | | PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|