| 2013-04-24 11:48:11 | 310 NORTH OLIVE AVENUE |
| | PERMIT #13040680 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE |
| | OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE |
| | HIGHWAY." |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | SHEET A-2: PROVIDE AN OCCUPANT LOAD CALCULATION FOR THE |
| | NEW CLASSROOM SPACES. |
| | |
| | SHEET A-2: PLANS INDICATE NEW FIRE RATED DOORS AND |
| | DUCTWORK FIRE DAMPERS; HOWEVER, THE WALL DETAIL DOES |
| | NOT INDICATE THIS WALL IS TO BE CONSTRUCTED WITH A |
| | 1-HOUR FIRE RESISTANCE RATING. |
| | |
| | SHEET A-2: IF NEW WALLS ARE INTENDED TO HAVE A FIRE |
| | RATING THEN EACH FIRE BARRIER SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC |
| | SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION |
| | DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA |
| | FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL." |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |