| Plan Review Notes For Permit 13040680 |
| Permit Number |
13040680 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-05-07 11:50:55 | 5-7-13 | | | 1. PROVIDE ONE LINE ELECTRICAL RISER DIAGRAM PER NEC | | | 215.5 | | | 2. SHOW SQUARE FOOTAGE OF BLDG ON DRAWINGS | | | 3. PROVIDE LIGHTING CONTROLS PER ENERGY CODE SECTION | | | 5.2.2 | | | 4. ALL DEMO ELECTRICAL CONDUCTORS SHALL BE REMOVED BACK | | | TO THE SOURCE IF NOT BEING RE-USED. CONDUIT SHALL BE | | | CUT FLUSH AND CAPPED. | | | VB |
|