Plan Review Notes
Plan Review Notes For Permit 13040680
Permit Number 13040680
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-25 12:18:22BUILDING PLAN REVIEW
 PERMIT: 13040680
 ADD:310 N OLIVE AVE FLOOR LEVEL
 CONT: COUNIHAW CONSTRUCTION LLC
 TEL: (561)722-6266
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/25/2013
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH ADMINISTRATIVE CODE CHAPTER 1,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 1) WHICH FLOOR IS THIS WORK TO BE COMPLETED ON?
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 OCCUPANCY LOAD.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS CORRIDORS T 1018.1.
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED
 5) IS THE BUILDING FIRE SPRINKLERED?
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 2) 2010 F BC-B 1031.3 1031.3
 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR SHALL BE
 RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR TRAFFIC;
 ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES (3.1 RAD)
 TO STOP AGAINST THE WALL. DOORS IN ANY POSITION SHALL
 NOT REDUCE THE REQUIRED CORRIDOR WIDTH BY MORE THAN
 ONE-HALF.
  
 3) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 4) IF THE BUILDING IS NOT FIRE SPRINKLERED, THEN THE
 CORRIDORS WILL NEED TO BE 1 HOUR FIRE RATERD, THE
 MECHANICAL PLANS DO NOT INDICATE FIRE DAMPERS IN THE
 CORRIDOR WALLS.FBC-B 716.5.2 FIRE BARRIERS. DUCTS AND
 AIR TRANSFER OPENINGS OF FIRE BARRIERS SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS INSTALLED IN
 ACCORDANCE WITH THEIR LISTING. DUCTS AND AIR TRANSFER
 OPENINGS SHALL NOT PENETRATE EXIT ENCLOSURES AND EXIT
 PASSAGEWAYS EXCEPT AS PERMITTED BY SECTIONS 1022.4 AND
 1023.6, RESPECTIVELY.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO