| Plan Review Notes For Permit 13040663 |
| Permit Number |
13040663 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-12-03 16:40:38 | BUILDING REVISION THIRD CHECKLIST. | | | CODE: 2007 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) WINDOW MULLIONS. | | | | | | DRAWINGS SUBMITTED (DWG NO 08-00125) ARE NOT A PRODUCT | | | APPROVAL. IF THERE IS NOT A CURRENT PRODUCT APPROVAL, | | | THEN MANUFACTURER MAY APPLY FOR A LOCAL PRODUCT | | | APPROVAL. PLEASE, CALL ME FOR INSTRUCTIONS ON HOW TO | | | APPLY FOR LOCAL PRODUCT APPROVAL. | | | | | | B) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS. | | | PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE | | | SPECIFIED CONNECTOR. | | | | | | INFORMATION SUBMITTED ARE NOT A PRODUCT APPROVAL. IF | | | THERE IS NOT A CURRENT PRODUCT APPROVAL, THEN | | | MANUFACTURER MAY APPLY FOR A LOCAL PRODUCT APPROVAL. | | | PLEASE CALL ME FOR INSTRUCTIONS ON HOW TO APPLY FOR | | | LOCAL PRODUCT APPROVAL. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ABOVE PRODUCT APPROVALS. | | | | | | 3- ENERGY CALCULATIONS SUBMITTED: | | | A) ENGINEER TO SIGN AND SEAL DOCUMENTS AS REQUIRED BY | | | CHAPTER 471 FLORIDA STATUTE. | | | | | | B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS | | | REQUIRED BY SEC. N1100.2.2 OF 2007 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|