| 2013-09-27 09:02:52 | BUILDING REVISION SECOND CHECKLIST. |
| | CODE: 2007 FBC. |
| | |
| | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) EXTERIOR INSWING DOORS AS SHOWN ON PLANS BY THE |
| | KITCHEN AREA. (ONLY PRODUCT APPROVAL FOR OUTSWING DOOR |
| | WAS PROVIDED AT THIS TIME). |
| | |
| | B) WINDOW MULLIONS. (STILL NONE SUBMITTED AT THIS |
| | TIME). |
| | |
| | C) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| | PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR. (STILL NONE SUBMITTED AT THIS |
| | TIME). |
| | |
| | D) PROVIDE INFORMATION SHOWING THAT DRAWINGS SUBMITTED |
| | FOR DOUBLE HUNG WINDOWS ARE PART OF A FLORIDA BUILDING |
| | COMMISSION (FBC) APPROVAL PACKAGE. IF THERE IS NOT |
| | CURRENT PRODUCT APPROVAL, THEN NEED TO APPLY FOR LOCAL |
| | PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED: |
| | (A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. (NO |
| | DONE). |
| | (B) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED |
| | BY CHAPTER 471 FLORIDA STATUTES. (NO DONE). |
| | (C) COORDINATE DOOR AND WINDOW MATERIAL WITH MATERIALS |
| | SHOWN ON PRODUCT APPROVALS SUBMITTED. (NO DONE). |
| | |
| | ****NOTE: NEW ITEMS: |
| | D) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WINDOWS AND GLASS IN DOORS SHOWING COMPLIANCE WITH THE |
| | U FACTOR AND SHGC FACTOR SHOWN ON ITEM #7. (SEC. |
| | 13-601.AB.1 OF 2007 FBC. |
| | |
| | F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. |
| | |
| | |
| | 4- OWES $103.00 REVISION FEES FOR TOTAL NUMBER OF |
| | DRAWINGS AND PRODUCT APPROVALS SUBMITTED (7 TOTAL). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |