| Plan Review Notes For Permit 13040634 |
| Permit Number |
13040634 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-22 13:32:23 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | | | | 1. SHEET A-2 SHOWS A PUMP LINE CONNECTING INTO A SINK | | | ARM ATTACHED TO A WET VENT. | | | P-712.3.5 EJECTOR CONNECTION TO THE DRAINAGE SYSTEM. | | | PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO | | | THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN | | | THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM | | | THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE | | | DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO | | | HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE | | | THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE | | | PIPING. | | | | | | 2. SHEET A-2 ONE SINK IS SHOWN CONNECTING TO THE VACUUM | | | SYSTEM. | | | INDIRECT WASTES | | | 802.1 WHERE REQUIRED. | | | FIXTURES NOT REQUIRED BY THIS SECTION TO BE INDIRECTLY | | | CONNECTED SHALL BE DIRECTLY CONNECTED TO THE PLUMBING | | | SYSTEM IN ACCORDANCE WITH CHAPTER 7. | | | | | | 3. PLEASE INCLUDE A WATER DIAGRAM. | | | 107.3.5.1.3 PLUMBING | | | 3. WATER SUPPLY PIPING | | | | | | 4. MED GAS IS NOT PART OF THIS REVIEW. A SEPARATE | | | APPLICATION, PLAN, EQUIPMENT SPECIFICATIONS, AND PERMIT | | | IS REQUIRED FOR THE AIR AND VACUUM SYSTEMS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|