Plan Review Notes
Plan Review Notes For Permit 13040634
Permit Number 13040634
Review Stop P
Sequence Number 1
Notes
Date Text
2013-04-22 13:32:23FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. SHEET A-2 SHOWS A PUMP LINE CONNECTING INTO A SINK
 ARM ATTACHED TO A WET VENT.
 P-712.3.5 EJECTOR CONNECTION TO THE DRAINAGE SYSTEM.
 PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO
 THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN
 THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM
 THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE
 DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE
 THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING.
  
 2. SHEET A-2 ONE SINK IS SHOWN CONNECTING TO THE VACUUM
 SYSTEM.
 INDIRECT WASTES
 802.1 WHERE REQUIRED.
 FIXTURES NOT REQUIRED BY THIS SECTION TO BE INDIRECTLY
 CONNECTED SHALL BE DIRECTLY CONNECTED TO THE PLUMBING
 SYSTEM IN ACCORDANCE WITH CHAPTER 7.
  
 3. PLEASE INCLUDE A WATER DIAGRAM.
 107.3.5.1.3 PLUMBING
 3. WATER SUPPLY PIPING
  
 4. MED GAS IS NOT PART OF THIS REVIEW. A SEPARATE
 APPLICATION, PLAN, EQUIPMENT SPECIFICATIONS, AND PERMIT
 IS REQUIRED FOR THE AIR AND VACUUM SYSTEMS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  