| Date |
Text |
| 2013-05-06 09:28:01 | 5-6-13 | | | 1. ANY RECEPT WITHIN 6FT OF A SINK OR BASIN MUST BE GFI | | | 2. MUST COMPLY WITH ARTICLE 517 OF THE NEC FOR PATIENT | | | CARE AREAS, BOTH ABOVE AND BELOW THE FLOOR | | | 3. INDICATE CIRCUIT NUMBEERS AT DEVICE LOCATIONS | | | | | | VB |
|