| 2013-04-25 11:48:39 | BUILDING PLAN REVIEW |
| | PERMIT: 13040634 |
| | ADD: 5707 S DIXIE HWY SUITE D |
| | CONT: ACECA CONSTRUCTION |
| | TEL: (561)574-7733 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/25/2013 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW NEW BREAK ROOM DOOR SWING AND ACHIEVE |
| | CODE COMPLIANCE WITH 2010 FBC-B 1008.1.9.11 |
| | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| | LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, |
| | NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR |
| | LANDING, WHEN FULLY OPEN. |
| | |
| | 2) THE DOOR BETWEEN THE WAITING ROOM AND CORRIDOR DOES |
| | NOT APPEAR TO HAVE 18 INCHES LATCH SIDE OF THE DOOR. |
| | PLEASE SEE 2010 FL ACCESSIBILITY CODE SECTION 404.2.4.1 |
| | & TABLE 404.2.4.1. |
| | |
| | 3) THE RECEPTION AREA COUNTER TOP WILL ALSO NEED TO |
| | MEET THE 2010 FLACCESSIBILTY CODE 904.3.3 CHECK WRITING |
| | SURFACES. |
| | WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY |
| | WITH 902.3. |
| | 2010 FL ACCESSIBILITY CODE 902.3 HEIGHT. THE TOPS OF |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |