Plan Review Notes
Plan Review Notes For Permit 13040633
Permit Number 13040633
Review Stop M
Sequence Number 2
Notes
Date Text
2013-07-03 10:45:30PASS PROVISO
 1) REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING
 2010 FLORIDA ENERGY CODE SUBMIT AS A REVISION.
 2) PROVIDE A LETTER FROM THE ENGINEER SHOWING THE BOLT
 SIZE FOR THE CURB TO ROOF TIE DOWN AND RTU TO CURB TIE
 DOWN.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M).
 SUBMIT AS A REVISION.