Plan Review Notes
Plan Review Notes For Permit 13040633
Permit Number 13040633
Review Stop M
Sequence Number 1
Notes
Date Text
2013-05-06 14:04:42PLANS DENIED
 1) CAN NOT READ ROOF CURB DETAIL ON THE PLANS.
 PROVIDE A LEGIBLE ROOF CURB DETAIL WITH BOLT SIZE.
 PROVIDE A RTU TO CURB DETAIL ALSO BY THE ENGINEER.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM, 606.3
 INSTALLATION AND 606.4.1 SUPERVISION.
 3) CHANGE OUT FORM IS REQUIRED
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  