Plan Review Notes
Plan Review Notes For Permit 13040580
Permit Number 13040580
Review Stop B
Sequence Number 1
Notes
Date Text
2013-04-16 11:41:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 THE DOCUMENTS PROVIDED DO NOT INCLUDE A PRODUCT NAME.
 SHOW COMPLIANCE FOR THE FOLLOWING REQUIREMENTS FOR THE
 PROPOSED UNDERLAYMENT:
  
 1. FBC 1207.2 AND 1207.3, THE TEST DATA SUBMITTED IS
 MISSING PAGE 1.
  
 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  