| Plan Review Notes For Permit 13040565 |
| Permit Number |
13040565 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-24 14:50:37 | 1801 PALM BEACH LAKES BOULEVARD | | | PERMIT #13040565 | | | MASTER #12100555 (POSSIBLY ADDRESSED AS 1721 PBL BLVD) | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****APPROVED WITH PROVISIONS***** | | | | | | SUBMIT PRODUCT DATA CUTSHEETS FOR BACKFLOW PREVENTERS. | | | DEVICES SHALL BE LISTED FOR FIRE PROTECTION USE. | | | | | | INSTALLATION, FLUSHING AND TESTING OF UNDERGROUND FIRE | | | MAINS SHALL COMPLY WITH NFPA 24 (2007 EDITION). | | | | | | FIRE MAINS AND FIRE DEPARTMENT CONNECTION LINES SHALL | | | HYDROSTATICALLY TESTED FOR 2-HOURS AT 200 PSI. | | | | | | HYDRANTS AND ADEQUATE WATER SUPPLY ARE REQUIRED PRIOR | | | TO BUILDING CONSTRUCTION OR STORAGE OF COMBUSTIBLES. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|