| 2013-05-07 16:09:39 | BUILDING PLAN REVIEW |
| | PERMIT: 13040466 |
| | ADD: 1025 26TH ST |
| | CONT: AHRENS COMPANIES |
| | TEL: (561)863-9004 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/30/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 102.1 THE SITE PUSH WALL DETAILS DOES NOT |
| | PROVIDE THE WIND DESIGN CRITERIA FOR THIS WIND ZONE AND |
| | THAT THE FOUNDATION MEETS THE MOMENT OF OVERTURNINGFOR |
| | THIS WIND SPEED. THE PRE ENGINEERED COMPONENT |
| | MANUFACTURER WILL NEED THIS INFORMATION TO SIZE AND |
| | DESIGN THE SHOP DRAWINGS FOR THIS WIND SPEED. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |