 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
  
 THE PERMIT APPLICATION INDICATES THE PROJECT ADDRESS AS
 701 SOUTH ROSEMARY AVENUE SUITE #137; HOWEVER, THE
 ARCHITECTURAL AND MEP SHEETS INDICATE AN ADDRESS OF 700
 SOUTH ROSEMARY AVENUE SUITE #A13. PLEASE COORDINATE THE
 CORRECT ADDRESS.
  
 SHEET A0.10: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A0.30: PROVIDE TACTILE SIGNAGE AT ALL REAR EXIT
 DOORS WITH EXIT SIGNS.
  
 SHEET A2.10: TRAVEL DISTANCE TO REAR FIRE EXTINGUISHER
 SHALL NOT EXCEED 75 FEET.
  
 SHEET A2.10: DOOR #112 SWINGS AGAINST THE FLOW OF
 TRAFFIC AND SERVES MORE THAN 50 PERSONS.
  
 SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK
 PENETRATING STOCK ROOM #113.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, ?FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.?
  
 GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE
 SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED.
 PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS -
 "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE
 FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS,
 ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL."
  