| Plan Review Notes For Permit 13040438 |
| Permit Number |
13040438 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-24 07:33:26 | PROVIDE DETAILS OF TRANSFORMER MOUNTING AND SUPPORT, | | | INCLUDING CLEARANCES | | | TIE TRANSFORMER TO BUILDING GROUNDING ELECTRODE SYSTEM | | | (GES) PER NEC 250 | | | TRANSFORMER GROUNDING AND CONNECTIONS TO BE PER 250.30 | | | LOAD CALCULATIONS SHOW NO MOTOR LOADS, AHU IS A MOTOR, | | | IS ANYTHING ELSE NOT SHOWN? | | | LL PLAN SHOWS HEAT IN EXCESS OF AC, IS HEAT IN THE LOAD | | | CALC AS AIR CONDITIONING? | | | AIC CALCULATION SOWS SINGLE CONDUCTOR USED FOR THE | | | CALCULATIONS WHILE THE VOLTAGE IS SYSTEM VOLTAGE? | | | TIME CLOCK MUST RETAIN PROGRAMMING FOR AT LEAST 10 | | | HOURS (BATTERY BACKUP) FLORIDA ENERGY CODE 505.2.4 |
|