Plan Review Notes
Plan Review Notes For Permit 13040438
Permit Number 13040438
Review Stop E
Sequence Number 1
Notes
Date Text
2013-04-24 07:33:26PROVIDE DETAILS OF TRANSFORMER MOUNTING AND SUPPORT,
 INCLUDING CLEARANCES
 TIE TRANSFORMER TO BUILDING GROUNDING ELECTRODE SYSTEM
 (GES) PER NEC 250
 TRANSFORMER GROUNDING AND CONNECTIONS TO BE PER 250.30
 LOAD CALCULATIONS SHOW NO MOTOR LOADS, AHU IS A MOTOR,
 IS ANYTHING ELSE NOT SHOWN?
 LL PLAN SHOWS HEAT IN EXCESS OF AC, IS HEAT IN THE LOAD
 CALC AS AIR CONDITIONING?
 AIC CALCULATION SOWS SINGLE CONDUCTOR USED FOR THE
 CALCULATIONS WHILE THE VOLTAGE IS SYSTEM VOLTAGE?
 TIME CLOCK MUST RETAIN PROGRAMMING FOR AT LEAST 10
 HOURS (BATTERY BACKUP) FLORIDA ENERGY CODE 505.2.4