| Plan Review Notes For Permit 13040437 |
| Permit Number |
13040437 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-04-23 11:32:29 | PLANS DENIED | | | 1) LANDLORD'S PLAN AND MECHANICAL PLAN | | | PERMIT # 13040438 DO NOT MATCH.LANDLORD PLAN | | | SHOWS MAKE UP AIR AND EXHAUST GOING TO LANDLORD'S | | | STORAGE. FIRE DAMPERS ARE REQUIRED AT THE MAKE UP AIR | | | AND EXHAUST WALL PENETRATION. | | | PER SECTION 607.5.2 FIRE BARRIERS. | | | LANDLORD'S PLAN SHOW FIRE DAMPERS AS NEW, | | | MECHANICAL PLAN SHOWS FIRE DAMPERS AS EXISTING. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|