| 2013-04-16 13:21:05 | 701 SOUTH ROSEMARY AVENUE - #137 |
| | PERMIT #13040437 |
| | SEE ALSO PERMIT #13040438 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PERMIT APPLICATION AND SHEET A-1 INDICATE THE |
| | PROJECT ADDRESS AS 701 SOUTH ROSEMARY AVENUE; HOWEVER, |
| | THE MEP SHEETS INDICATE AN ADDRESS OF 700 SOUTH |
| | ROSEMARY AVENUE. PLEASE COORDINATE THE CORRECT ADDRESS. |
| | |
| | SHEET M-1: NO FIRE DAMPER PROVIDED IN DUCTWORK |
| | PENETRATING LANDLORD STORAGE ROOM #102. |
| | |
| | GENERAL: EACH FIRE BARRIER SHALL BE PERMANENTLY |
| | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| | DOORS WITH EXIT SIGNS. |
| | |
| | GENERAL: LANDLORD STORAGE #102 DOES NOT INDICATE ANY OF |
| | THE FOLLOWING INFORMATION: COMMODITY CLASS OF |
| | COMBUSTIBLES (PER NFPA 13), QUANTITY, STORAGE |
| | ARRANGEMENT (RACKS, PILE, BIN, ETC.), STORAGE HEIGHT, |
| | AISLE LAYOUT, ETC. |
| | |
| | GENERAL: PROVIDE PORTABLE FIRE EXTINGUISHERS. |
| | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC |
| | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER |
| | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT |
| | EXCEED 75 FEET. |
| | |
| | GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT, |
| | SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE |
| | REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS |
| | FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC |
| | FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE CODE |
| | SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| | DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| | WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| | APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| | OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| | TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| | DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| | INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| | |
| | GENERAL: NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. |
| | PER FBC SECTION 907.1.1 CONSTRUCTION DOCUMENTS - |
| | "CONSTRUCTION DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE, THE |
| | FLORIDA FIRE PREVENTION CODE, AND RELEVANT LAWS, |
| | ORDINANCES, RULES AND REGULATIONS, AS DETERMINED BY THE |
| | BUILDING OFFICIAL." |
| | |