| 2013-04-13 11:41:29 | BUILDING PLAN REVIEW |
| | PERMIT: 13040437 |
| | ADD: 701 S ROSEMARY AVE SUITE 137 |
| | CONT: TBD |
| | TEL: (561)856-6655 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: APRIL 13/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) PLANS FOR CITY PLACE REQUIRE A REVIEW BY CITY PLACE |
| | STAFF AND REVIEW OF APPROVAL STAMP ON THE PLANS BEFORE |
| | SUBMITTAL TO THE CITY FOR REVIEW AND ISSUANCE. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) THE SHEET A-1 INDICATES A NEW LANDLORD STORAGE AREA, |
| | BUT NO PLANS WERE SUBMITTED WITH THE EXISTING FIRE |
| | SPRINKLER LAY OUT AND THE NEW FIRE SPRINKLER LAYOUT |
| | SINCE THE NEW TENANT SEPERATION WALL WILL IMPEDE THE |
| | FIRE SPRINKLER COVERAGE. |
| | 2010 FBC-B 903.2.7 MERCANTILE |
| | 2010 FBC-B 903.2.9 S-1 STORAGE |
| | |
| | 3) THE NEW STORAGE AREA DOES NOT INDICATE ANY EMERGENCY |
| | LIGHTING DEVICES IN EITHER THE NEWLY FORMED TENANT |
| | SPACE OR COMMON EXIT PASSAGE WAY. 2010 FBC-B 1006.1.1 |
| | MEANS OF EGRESS ILLUMINATION. 1006.1.6.2 BATTERY |
| | OPERATED ELECTRIC LIGHTS. |
| | |
| | 4) THE PLANS ARE ALSO MISSING EXIT LIGHTING AND |
| | SIGNAGE, 2010 FBC-B 1006.3.1 EVERY EXIT SIGN SHALL BE |
| | SUITABLY ILLUMINATED BY A RELIABLE LIGHT SOURCE. |
| | |
| | 5) THE PLANS ARE ALSO MISSING EXIT DOOR TACTILE |
| | SIGNAGE, 2010 FBC-B 1006.3.4. |
| | |
| | 6) THE TENANT BUILD-OUT PLAN UNDER PERMIT # 13040438 |
| | AND THIS PLAN HAS A DISCREPANCY AS TO WHERE THE TENANT |
| | SEPERATION WALL AND DOORWAY ARE LOCATED AND THE SHARED |
| | EXIT PASSAGE WAY BEGIN. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 7 ) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |