| 2013-04-22 08:04:18 | BUILDING PLAN REVIEW |
| | PERMIT: 13040405 |
| | ADD: 801 S OLIVE DR # 906 |
| | CONT: COUNIHAN CONST |
| | TEL: (561)722-6266 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/22/2013 |
| | ACTION: BUILDING PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) THIS BUILDING IS A HIGHRISE A BUILDING TYPE IA. |
| | SHEET A1 INDICATES THE REMOVAL OF ALL FLOORING WITHIN |
| | THE UNITPLEASE SUBMIT DOCUMENTATION OF CODE COMPLIANCE |
| | FOR THE FOLLOWING: |
| | |
| | 1A) COMBUSTIBLE MATERIAL IN TYPE I AND II |
| | CONSTRUCTION603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 1A) FOR STONE, MARBLE OR CERAMIC TILE , 603.1.3.2 |
| | EXCEPTION # 1.EXCEPTION: 1. INSULATION PLACED BETWEEN |
| | TWO LAYERS OF NONCOMBUSTIBLE MATERIALS WITHOUT AN |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 100. |
| | |
| | 1B) WOOD FLOORS IN HIGH RISE BUILDINGS 805.1.2 WOOD |
| | FINISH FLOORING. |
| | WOOD FINISH FLOORING IS PERMITTED TO BE ATTACHED |
| | DIRECTLY TO THE TOP SURFACE OF FIRE-RESISTANCE-RATED |
| | FLOOR ASSEMBLIES . PROVIDE MANUFACTURERS INSTALATION |
| | INSTRUCTIONS. |
| | |
| | 2) 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |